Войти:

Allied Air Enterprises WARM AIR GAS FURNACE A95UH

Скачали: 13Размер: 3 mb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

9. After determining that each appliance remaining connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use. 506724-01 Issue 1108 Page 45 of 57 Page 46 of 57 Issue 1108 506724-01 Other Unit Adjustments Primary Limit The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment

Allied Air Enterprises WARM AIR GAS FURNACE A93UH

Скачали: 9Размер: 3 mb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

Cement should be applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe. 7. Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. Do not turn ABS or cellular core pipe. NOTE: As

Allied Air Enterprises WARM AIR GAS FURNACE 95G1UH

Скачали: 1Размер: 3 mb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

intake or exhaust pipe length. What is the altitude? 7 Furnace capacity? FIGURE 21 MINIMUM VENT PIPE LENGTHS IMPORTANT Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze-ups and may block the terminations. *Any approved termination may be added to the minimum length listed. **This gas furnace must have 3” to 2” reducing ell (supplied or field replacement Canadian kit) installed directly into unit flue collar. TABLE 4 506724-01 Issue 1108 Page 17

Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH

Скачали: 1Размер: 3 mb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

ROOF TERMINATED EXHAUST PIPE SIDE WALL TERMINATED EXHAUST PIPE (ALTERNATE LOCATION) FURNACE sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have

Allied Air Enterprises Upflow

Скачали: 2Размер: 901 kb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. 8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Insta

Allied Air Enterprises Downflow or Horizontal 2 Stage Heat Variable Speed Gas Fired Non-Condensing Warm Air Furnace

Скачали: 6Размер: 901 kb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

3 Furnace Wiring Specifications .......................... 5 Introduction ....................................... 6 Location/Placement.................................. 7 Air for Combustion & Ventilation ........................ 8 Ducting .......................................... 11 Venting .......................................... 12 Electrical Connections................................ 15 Gas Connections ................................... 16 Control Board & Variable Speed Motor Features .

Allied Air Enterprises A95UH

Скачали: 1Размер: 719 kb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

* Use wall support every 24” (610 mm). Use two wall supports if extension is greater than 24” (610 mm) but less than 48” (1219 mm). NOTE: One wall support must be 6” (152 mm) from top of each pipe (intake and exhaust). FIELD SUPPLIED WALL TERMINATION See venting Table 5 for maximum venting lengths with this arrangement. * Use wall support every 24” (610 mm). Use two wall supports if extension is greater than 24” (610 mm) but less than 48” (1219 mm). NOTE: One wall support must be 6” (152 mm) fro

Allied Air Enterprises A95DF

Скачали: 1Размер: 3 mb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is insta

Allied Air Enterprises A93UH

Скачали: 0Размер: 719 kb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result. Installation Clearances Top/Plenum 1 in. (25 mm) * Front 0 Back 0 Sides 0† Vent 0 Floor 0‡ * Front clearance in alcove installation must

Allied Air Enterprises A93DF

Скачали: 2Размер: 3 mb    Производитель: Allied Air Enterprises  
Категория: Электрообогреватели

Units installed at altitudes of 4501 - 10,000 feet (1373 to 3048 m) require a pressure switch change which can be ordered separately. Table 14 lists conversion kit and pressure switch requirements at varying altitudes. The combustion air pressure switch is factory-set and requires no adjustment. Page 36 of 48 Issue 1109 506725-01 Burner Orifice Conversion Kits at Varying Altitudes Unit Size 0 - 7,500 ft (0 - 2,286 m) 7,501 - 10,000 ft (2,286 - 3,038 m) Natural to LP/Propane LP/Propane to Natural





Категории