— — 2. Check for line voltage power at the oil primary control. Voltage should be 120 Vac. — — 3. Check indicator light with burner off, no call for heat (no flame). Indicator light is on. Cad cell or controller is defective, sees external light or connections are shorted. Go to step 4. Indicator light is off. Go to step 5. 69-1233—2 6 R7184A,B,P,U INTERRUPTED ELECTRONIC OIL PRIMARY R7184A,B,P,U INTERRUPTED ELECTRONIC OIL PRIMARY 4. Shield cad cell from external light. Indicator light turns off.