К этому устройству также есть другие инструкции:

Фрагмент инструкции





9.
Program the midplane EEPROM with the enclosure serial number.
This can be done on a bench with power applied to the power
Installing the midplane
supplies, or after the enclosure has been installed in a rack and
power applied.
1.
Place the midplane in the enclosure, and carefully press the
midplane connectors into their mating backplane connectors.
2.
With the thumbscrew mounting holes aligned with the holes in the
NOTE:
enclosure chassis, tighten the midplane thumbscrews.
The enclosure serial number can only be transferred to an
unprogrammed midplane EEPROM that resides on a spare
3.
Reattach the power UID cable and interconnect board cable to the
midplane provided by HP. Once the EEPROM has been
midplane.
set, it cannot be changed.
4.
Reattach the top access panel.
5.
Reinstall the I/O modules.
a.
Insert one end of a serial cable (part number 259992–001)
6.
Reinstall the fan modules.
into a laptop serial port, and insert the other end into the serial
7.
Reinstall the power supplies
port of either I/O module.
8.
Write down the 10–digit enclosure serial number found on the rear
b.
Using a terminal emulation program (for example,
of the enclosure above the left fan module (see Figure 8).
HyperTerminal), set the baud rate to 115200.
c.
Enter the command ssnSet XXXXXXXXXX, where
XXXXXXXXXX is the 10–digit enclosure serial number obtained
in Step 8.
Product Number: AG638A
Serial Number: xxxxxxxxxxx
CAUTION:
You must ensure that the enclosure serial number is
correct when asked to confirm the number. Once the
number is set, you cannot change it.
Product Number: AG638A
Serial Number: xxxxxxxxxxx
d.
When prompted to confirm the serial number, enter yes. If the
number is incorrect, enter no, and reenter the serial number.
The confirmation screen times out after 10 seconds.
10. Reinstall the enclosure into the rack, and attach the bezel ears.
15822
11. If the disk drives were previously removed from the enclosure,
Figure 8 Enclosure serial number location
reinsert them.
12. Reattach the power, Ethernet, and Fibre Channel cables to the
enclosure components.
13. Press the power button on the power UID bezel (located at rear of
enclosure) and hold it down until power is applied to the disk
enclosure. If more disk enclosures are in your array, power them
up the same way.
14. Press the power button on the power UID bezel of the controller
enclosure and hold it down until power is applied.
Verifying proper operation
NOTE:
Wait three minutes after powering up the enclosure for the
system to check component status.
Verify the status LEDs of the hard drives, I/O modules, and fan modules
for proper operation as described in Table 1 and Table 2.
Page 4


...

Эта инструкция также подходит к моделям:
Устройства обработки данных - HP 4400 Dual Controller Enterprise Virtual Array (1.36 mb)
Устройства обработки данных - HP EVA6400 Array (1.36 mb)
Устройства обработки данных - HP EVA6400 for Storage Centric Rack (1.36 mb)
Устройства обработки данных - HP EVA8400 Array (1.36 mb)

Напишите ваш отзыв об устройстве



Текст отзыва
Ваше имя:
Введите две цифры:
capcha





Категории