After connected, proceed with the following. Static Pressure Check: Place the flare gasket and blank flare cap on the device. Open ^ turn valve and read pressure gauge. If pressure reads below 25 PSIG there is no need to go any further. Correct the supply problem before proceeding. If the pressure exceeds 60 PSIG we recommend a water pressure regulator be installed. Flowing Pressure Check: Estimate the water usage of all equipment connected to the water delivery system (e.g. IntelliCarb = 125 GPH, a two flavor Pinnacle = 100 GPH, Total = 225 GPH). Select the Number 3 (13/64”) orifice to insure that it can supply more than the 225 GPH required to operate both units. Close the ^ turn valve and remove the blank flare cap. Install the flare cap with the proper size orifice to match the flow rate desired and open the ^ turn valve. Direct the water flow in to a large container, sink, or floor drain for at least 20 seconds. Read the pressure gauge while the water is flowing. If the gauge maintains 25 PSIG or higher, the water supply is sufficient for the flow rate that was selected. Part Number Stamp Number Orifice Diameter Flow Rate in Gallons Per Hour (GPH) at 25 PSIG 620718954 1 1/8” 100 GPH 620718955 2 3/16” 200 GPH 620718956 3 13/64” 300 GPH Release Date: August 23, 2004 © 2004, IMI Cornelius Inc. - 1 - Revision: A Publication Number: 629088461INS...