Войти:
Оценок - , средний балл: ( )

Инструкция по эксплуатации Bosch, модель LC58655GB/01

Производитель: Bosch
Размер: 634.77 kb
Название файла:

Язык инструкции:en

Документ загружается, подождите пожалуйста
Документ загружается, подождите пожалуйста

Фрагмент инструкции


All packaging materials are environmentally friendly and recyclable. Please contribute to a better environment by disposing of packaging materials in an environmentally-friendly manner. Please ask your dealer or inquire at your local authority about current means of disposal. The extractor hood can be used in exhaust air or circulating air mode. Always mount the extractor hood over the centre of the hob. Minimum distance between electric hob and bottom edge of extractor hood: 550 mm, Fig. 1. The extractor hood must not be installed over a solid fuel cooker – a potential fire hazard (e.g. flying sparks) – unless the cooker features a closed, non-removable cover and all national regulations are observed. The smaller the gap between the extractor hood and hotplates, the greater the likelihood that droplets will form on the underside of the extractor hood. Additional information concerning gas cookers: When installing gas hotplates, comply with the relevant national statutory regulations (e.g. in Germany: Technische Regeln Gasinstallation TRGI). Always comply with the currently valid regulations and installation instructions supplied by the gas appliance manufacturer. Only one side of the extractor hood may be installed next to a high-sided unit or high wall. Gap at least 50 mm. Minimum distance on gas hotplates between the upper edge of the trivet and lower edge of the extractor hood: 650 mm, Fig. 1. Prior to installation Exhaust-air mode 120150 120 150 280 260 550 590 600/700/900 mind.36 674-1060 mind.128 48 mind. 600 520 The exhaust air is discharged upwards through a ventilation shaft or directly through the outside wall into the open. DExhaust air should neither be directed into a smoke or exhaust flue that is currently used for other purposes, nor into a shaft that is used for ventilating rooms in which stoves or fireplaces are also located. Exhaust air may be discharged in accordance with official and statutory regulations only (e.g. national building regulations). Local authority regulations must be observed when discharging air into smoke or exhaust flues that are not otherwise in use. DWhen the extractor hood is operated in exhaust-air mode simultaneously with a different burner which also makes use of the same chimney (such as gas, oil or coal-fired heaters, continuous-flow heaters, hot-water boilers) care must be taken to ensure that there is an adequate supply of fresh air which will be needed by the burner for combustion. Safe operation is possible provided that the underpressure in the room where the burner is installed does not exceed 4 Pa (0.04 mbar). This can be achieved if combustion air can flow through non-lockable openings, e.g. in doors, windows and via the airintake/ exhaust-air wall box or by other technical measures, such as reciprocal interlocking, etc. If the air intake is inadequate, there is a risk of poisoning from combustion gases which are drawn back into the room. An air-intake/exhaust-air wall box by itself is no guarantee that the limiting value will not be exceeded. Note: When assessing the overall requirement, the combined ventilation system for the entire household must be taken into consideration. This rule does not apply to the use of cooking appliances, such as hobs and ovens. Unrestricted operation is possible if the extractor hood is used in recirculating mode – with activated carbon filter. If the exhaust air is going to be discharged into the open, a telescopic wall box should be fitted into the outside wall. Prior to installation For optimum extractor hood efficiency: . Short, smooth air exhaust pipe. . As few bends in the pipe as possible. . Diameter of pipe to be as large as possible and no tight bends in pipe. If long, rough exhaust-air pipes, many pipe bends or smaller pipe diameters are used, the air extraction rate will no longer be at an optimum level and there will be an increase in noise. . Round pipes: We recommend Internal diameter: 150 mm (at least 120 mm). . Flat ducts must have an internal cross- section that equates to that of round pipes. There should be no sharp bends. l120 mm approx. 113 cm2 l150 mm approx. 177 cm2 . If pipes have different diameters: Insert sealing strip. . For exhaust-air mode, ensure that there is an adequate supply of fresh air. Circulating-air mode . With activated carbon filter if exhaust-air mode is not possible. The complete installation set can be obtained from specialist outlets. The corresponding accessory numbers can be found at the end of these operating instructions. Connecting a l150 mm exhaust-air pipe: . Mount the pipe directly onto the air outlet on the hood. Connecting a l120 mm exhaust-air pipe: . Attach the reducing connector directly to the air pipe. . Attach the exhaust-air pipe to the reducing connector. 280 260 550 590 600/700/900 mind. 128 766-1 155 mind.34 48 520 Prior to installation Preparing the wall . The wall must be flat and perpendicular. . Ensure that the wall is capable of providing a f...

Эта инструкция также подходит к моделям:
Вытяжки - LC58750GB/01 (634.77 kb)
Вытяжки - LC58755GB/01 (634.77 kb)
Вытяжки - LC58955GB/01 (634.77 kb)

Напишите ваш отзыв об устройстве



Текст отзыва
Ваше имя:
Введите две цифры:
capcha





Категории