Войти:
Оценок - 3, средний балл: 4 ( )

Инструкция по эксплуатации Bock s, модель 150

Производитель: Bock s
Размер: 77.25 kb
Название файла: 661a31b8-25ae-40c5-9e2a-57bd2c55b78b.pdf
Язык инструкции:en
Перейти к скачиванию



Фрагмент инструкции


Flue Tubes: Flue tubes constructed of steel minimum, 1/8 in. thick, 6 in. OD by 35 in. long, and provided with fins welded in a spiral pattern. Model Number of Flues 150-400 3 200-450 3 150-600 5 200-650 5 150-800 7 200-850 7 200-1150 10 250-1250 12 250-1500 14 WARNING WARNING CAUTION WATER PIPING GAS PIPING OIL PIPING MOUNTING THE BURNER CONNECT TO THE CHIMNEY Improper installation, adjustment, alteration, service or maintenance can cause serious injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer or service agency. If the information in these instructions is not followed exactly, fire or explosion may result and can cause property damage, personal injury or death. Do not install on combustible flooring. Minimum clearance to combustible construction is: SIDES: 6”; BACK: 6”; FRONT: 24”. Install in accordance with all local codes. In the absence of local codes, refer to National Fuel Gas Code and/or NFPA 31 or ANSI Z21.10.1. Install unions and shut-off valves on both hot and cold water lines. A temperature and pressure (T&P) relief valve has been installed at the factory. Install a discharge line from the relief valve outlet to a suitable drain. Arrange the line without restriction to allow for complete drainage of both the relief valve and line. Do not install a check valve in the cold water line. If backflow preventers or pressure regulators are installed, be sure to make provision for expansion of water when heated by installing either a thermal expansion valve or an expansion tank in the system. All piping must comply with local codes/ordinances or National Fuel Gas Code & NFPA No. 54 Install a sediment trap or drip leg in the supply line to the burner. Install a union in the gas line adjacent to and upstream from the control manifold and downstream from the manual main shut-off valve. A 1/8” NPT plugged tapping accessible for test gauge connection must be installed immediately upstream of the gas supply connection to determine the gas supply pressure to the burner. Install a manual shut-off valve in the gas supply line external to the water heater. The gas line should be a separate supply direct from the meter to the burner. Use new pipe that is free of cutting burrs and well-supported. Use pipe dope (approved for all gasses) on male threads only. When pressure testing the gas supply piping system at less that 1/2 psig., close the manual gas shut-off valve to the heater. If test pressures are to exceed 1/2 psig., the water heater and its manual shut-off valve must be disconnected from the system. Be sure gas service and meter are adequately sized. All heaters covered by this manual are equipped with two-stage fuel pumps. They require a two pipe system, suction and return. The fuel pumps have the bypass plug installed, which requires a two- pipe system using 5/8” O.D. soft copper tubing. For gravity flow system (oil supply above the burner), if a one-pipe system is used the bypass plug should be removed. On the larger burners and all dual fuel burners, a two-pipe system is required. For multiple heater installations, run a separate suction and return line for each heater if possible. Where the combined lift in feet and horizontal run exceeds 100’, install a booster pump as near to the supply tank as possible. Return lines must be the same diameter as suction lines and extend close to the bottom of the storage tank, but stop slightly above the suction lines. Use a minimum of fittings, making bends in tubing with as large a radius as possible. Always use flared fittings, not compression fittings. If pipe is used instead of tubing, do not connect the burner to the pipe – use copper tubing and form a coil before attaching to the burner. The burner is shipped separately. Unpack and examine to be sure the unit is in good condition. Install on the water heater using the mounting bolts provided. On larger burners, an additional pedestal is supplied to support the burner. Make sure there are no obstructions in front of the burner and that the burner is not protruding into the combustion area. Using “L” or “A” type venting, connect the heater to the chimney. Do not reduce the smoke pipe diameter; use the same size smoke pipe as the heater flue pipe. Run a separate connector from the heater to the chimney where possible. If the heater must be joined to another oil appliance breaching before going into the chimney, enlarge the existing breaching to accommodate the extra volume of gases from the heater. The entrance into the breaching should be at a 45° angle. COMBUSTION AIR VENTILATION AIR NOTE: All ducts must have the same cross sectional area as the free area of each opening to which they connect. The minimum side dimension of a rectangular duct must be no smaller than three (3) inches. Caution: Operation of exhaust fans, ventiliating systems, power burners, induced draft systems, or fireplaces may create conditions that require special attention...

Эта инструкция также подходит к моделям:
Водонагреватели - 200 (77.25 kb)
Водонагреватели - 250 (77.25 kb)

Напишите ваш отзыв об устройстве



Текст отзыва
Ваше имя:
Введите две цифры:
capcha





Категории