1: Reposition the Tabs as Necessary (see step 10) to hold the Power Vent in position. Note: While twisting you may notice some roughness, this is due to a tight seal between the 6” vent and the Power Vent flue box. 12. Re-mount the access panel. 13. Re-mount the front door along with the knurled screw on the heater. TOP VIEW EXHUAST OUTLET REAR VIEW LEFT SIDE FRONT VIEW Note: The 90° elbow may be used as a termination cap. Fig. 2: Draft Assembly 6 Fig. 3: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations U.S. Installations1 Canadian Installations2 A Clearance above grade, veranda, porch, deck, or balcony 1 ft (30 cm) 1 ft (30 cm) B Clearance to window or door that may be opened 4 ft (1.2m) below or to side of opening; 1 foot (30 cm) above opening 3 ft (91 cm) C Clearance to permanently closed window * * D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft (61cm) from the centerline of the terminal 5 ft (1.5m) * E Clearance to unventilated soffit * * F Clearance to outside corner * * G Clearance to inside corner 6 ft (1.83m) * H Clearance to each side of center line extended above meter/regulator assembly * 3 ft (91 cm) within a height 15 ft above the me- ter/regulator assembly I Clearance to service regulator vent outlet * 6 ft (1.83m) J Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 4 ft (1.2m) below or to side of opening; 1 ft (30 cm) above opening 3 ft (91 cm) K Clearance to mechanical air supply inlet 3 ft (91 cm) above if within 10 ft (3m) horizontally 6 ft (1.83m) L Clearance above paved sidewalk or paved driveway located on public property 7 ft (2.13m) 7 ft (2.13m) t M Clearance under veranda, porch, deck or balcony * 12 in. (30 cm) TT 1 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code 2 In accordance with the current CAN/CGA-B149 Installation Codes t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves both dwellings TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and underside of veranda, porch, deck or balcony is greater than 1 ft (30cm) * Clearances in accordance with local installation codes and the requirements of the gas supplier Table B: Vent/Air Inlet Termination Clearances 7 Wiring a Power Vent Assembly 90 Degree Elbows 45 Degree Elbows to an Appliance with IID Maximum Maximum Quantity Quantity Length (ft) Length (ft)Ignition 1 30 1 35 WARNING: Disconnect all electrical power to the 2 20 2 30 unit before servicing to avoid potential shock injury 3 10 3 25 or damage to the unit. To change voltages, follow wiring diagram for correct voltage connections. Table C: Reduced Maximum Equivalent Vent Run Improper wiring connections can burnout the relay and blower motor. Venting The vent pipe must be the same size or one size larger than what is indicated. The D-2 Power Vent is capable of 360-degree discharge rotation and operates with a positive vent static pressure and with a vent gas temperature less than 400°F. The total length of horizontal run shall not exceed an equivalent of 40 feet including termination cap. For all cases, each 90-degree elbow reduces the maximum horizontal vent run by 10 feet and each 45-degree elbow in the vent run reduces the maximum vent run by 5 feet. See the table below for maximum vent lengths using 90-degree and 45-degree elbows. The D-2 Power Vent uses positive pressure to push flue gases through the vent pipe to the outside. The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is recommended that: a) The vent be installed with a slight downward slope of not more than 1/4” per foot of horizontal run to the vent terminal. b) The vent be insulated through the length of horizontal run. For appliances installed in extreme cold climate, it is recommended that: a) The vent be installed with a slight upward slope of not more than 1/4” per foot of horizontal run to the vent terminal. In this case, an approved condensate trap must be installed per applicable codes. b) The vent be insulated through the length of the horizontal run. 4" DIAMETER LEFT SIDE Fig. 4: Draft Assembly The Raypak Power Vent operates with a positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent and as such it is listed as a CATEGORY III appliance. Exception: When a Power Vent is connected to a vertical vent of sufficient height to generate a negative draft in the system. Consult sizing guide or factory. The D-2 Power Vent assembly is suitable for through the wall venting, and for connection to smaller size vent...