Войти:
Оценок - 3, средний балл: 4 ( )

Инструкция по эксплуатации InSinkErator, модель MS MS

Производитель: InSinkErator
Размер: 875.72 kb
Название файла: a024339d-af2e-483d-ae66-20270b2ffeda.pdf
Язык инструкции:en
Перейти к скачиванию



Фрагмент инструкции


See Table 1 for approved disposer and control center combinations. The control center operates the disposer. Its main functions are: • To start and stop the disposer. • To start the water flow to the disposer. Model Waste Disposer Model MS-4 MS-5 SS50-26, SS75-27, SS100-28, SS125-25, SS150-34, SS150-38, SS200-27, SS200-31 MS-5 SS50-27, SS75-28, SS100-29, SS125-26, SS150-36, SS150-39, SS200-29, SS200-32, SS300-25, SS300-27, SS500-28, SS500-29, SS500-30 MS-6 SS50-27, SS75-28, SS100-29, SS125-26, SS150-36, SS150-39, SS200-29, SS200-32, SS300-25, SS300-27, SS500-28, SS500-30, SS750-13, SS750-15, SS1000-10, SS1000-11, SS1000-12 Table 1. Approved Disposer and Control Center Combinations Model Part No. Voltage Phase HP MS-4 14356 120V 1 1/2-2 MS-5 14356A 208-230V 1 1/2-2 MS-5 14356A 208-230V 3 1/2-5 MS-6 14356B 380/460V 3 1/2-10 Table 2. Electrical Specifications FEATURES ENCLOSURE NEMA 4 construction. PUSH BUTTON OPERATION Push Green button to start disposer. Push Red button to stop disposer. MOUNTING THE CONTROL CENTER Use the flanges at the back of the control center enclosure and only mount panel in the upright vertical position. See Figure 1. Locate control center within sight of disposer per local codes. Locate any remote control station within sight of disposer per local codes. If box is mounted to the sink table, recess the box so that the buttons do not extend beyond the table's edge. Figure 1. Control Center Dimensions PROPERTY DAMAGE Use of more than two solenoid valves will affect the overall function of the MS control center. Extra solenoid valves will cause a reduction in voltage and solenoid actuation will not occur. 3 Plumbing Connections Figure 2. Typical Installation Diagram PLUMBING CONNECTIONS The flow control valve, syphon breaker and solenoid valve are supplied with all complete disposer packages (packed separately). Make certain that the solenoid valve supplied is the proper voltage. Make certain that the valves are plumbed according to water flow direction arrows marked on valves or the valves will not function properly. The flow control valve regulates all water flowing into the disposer. This conserves water and prevents overloading. Check direction of water flow arrows. Syphon breaker must be installed above the sink flood place per local plumbing codes. Check direction of water flow arrows. 4 and permanently grounded. • A properly fused disconnect must be installed at the electrical supply source for the control center. ELECTRICAL CONNECTIONS Connect the incoming line power and disposer motor to the labeled terminal block in the control center. Use appropriate voltage and phase electrical connection diagrams at the back of this manual. Wire the disposer motor for the correct voltage using the connection diagram inside the motor terminal box. Make sure the solenoid valve is the same voltage as the control panel and supply power. Connect water solenoid valve as shown in the wiring diagrams on pages 7, 8, 9, and 10. Wire per local electrical code using 7/8" diameter holes in bottom of control center cabinet and install NEMA 4 watertight electrical connectors (not supplied). After completing the connections, secure cover. Replace disposer motor cover. TIME DELAY RELAY (Optional, not supplied with MS) The time delay relay may be used with the MS to delay solenoid valve shut-off, providing a post flush. This helps prevents drain line stoppages and is beneficial when ground food waste must travel through many bends or a long horizontal run. It is adjustable from 0 to 10 minutes and factory set to provide approximately a 5 minute delay. To adjust, SHUT OFF ELECTRIC POWER. Inside unit, locate the adjustment potentiometer. Turn clockwise to increase delay. Turn counterclockwise to decrease delay. See Figures 4 and 5 for wiring. Ensure the voltage rating on the time delay relay and solenoid valve are the same as the disposer motor and line voltage. Electrical Connections ELECTRIC SHOCK • Turn off the electrical supply to the disposer before attempting any work on it. Use a voltmeter or circuit tester to ensure that power is off. • All installation work must conform to local plumbing and electrical codes. • All control centers and disposers must be carefully PROPERTY DAMAGE • Ensure that control center voltage and phase match the disposer motor and electrical supply. Check name plates on disposer and control centers for voltage and phase specifications. • Refer to the control center wiring diagrams in this manual for correct connection. • Use NEMA 4 watertight electrical connectors (not supplied) when making electrical connections to the control center. 1 3 6 4 Time Adjustment Knob Figure 3. 120V or 208/230V Time Delay Relay Figure 4. Time Delay Relay Connections - 120V or 208/230 V Figure 5. Time Delay Relay Connection - 460V, 3-phase only 5 Operating Instructions/Troubleshooting PERSONAL INJURY • Allow only trained personnel to operate disposer. • Use baffles and guarding to avoid splashing and e...


Напишите ваш отзыв об устройстве



Текст отзыва
Ваше имя:
Введите две цифры:
capcha





Категории