Фрагмент инструкции


The detector, which is a combined maximum/rate-of-rise heat detector, is assigned to class A1R and can be used up to a maximum room height of 7.5m. Conventional technology is used for alarm transmission to the fire detection control panel. In conjunction with Specifications Ignition protection intrinsically safe Ex classification EEx ia IIB T5 Current consumption typ. 100mA (quiescent) Alarm temperature 60°C (maximum-heat component) Ambient temperature -10°C to +43°C (continuous operation) Relative humidity 10 - 93% (no condensation) Dimensions 0 x H 104 x 54 (mm) Colour cream Weight 80g Approval BASEEFA03ATEX0155X VdS G296050 Order number 242015 Order name IS Thermal ROR Detector/Conv./400/SS 5451EIS the Safety Barrier ES58-2, the detector reaches the given Ex classification. The two LEDs with 360° visibility indicate the activated condition of the detector. A detector function test can be conveniently conducted using a magnet or a detector test device. The detector can be attached to various bases and it can be protected against theft. Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX. +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED 5451EÍS DBL LST EN 0804.PDF • PAGE 1...