3.08 CHILLED WATER A. The unit shall be piped in accordance with the highest commercial quality procedures. All exposed piping shall be insulated copper, type "L". All pipe forming shall be tool bent with proper bend radii to prevent tube flattening in the curve. The chilled water piping shall be insulated with closed cell neoprene thermal insulation. The chilled water flow shall be controlled by a 2- or 3way valve with a 24 VDC Actuator. InRoom Precision AC Tech Data Manual 3.09 FLUID COOLER A.