Войти:
Оценок - 1, средний балл: 4 ( )

Инструкция по эксплуатации GE, модель 10 AZA

Производитель: GE
Размер: 843.11 kb
Название файла: a97168d4-866d-4a40-b34c-86e70e19b459.pdf
Язык инструкции:en
Перейти к скачиванию



Фрагмент инструкции


21 Safety Instructions Operating Instructions Care and Cleaning Installation Instructions Troubleshooting Tips Consumer Support Through-the-wall installation. Read these instructions completely and carefully. Consumer Support Troubleshooting Tips Installation Instructions Care and Cleaning Operating Instructions Safety Instructions 1 Preparation of the Opening in the Wall Make certain a wall receptacle is available close to the hole location or make arrangements to install a receptacle. The cord length for the 115-volt models is 72. to the right and 47. to the left. For the 230/208-volt models the cord length is 65. to the right and 39. to the left. Support Requirements for the Air Conditioner The air conditioner wall case may be installed flush with the inside wall or flush with the outside wall. The finished sides of the opening should be structural wall members. Lintel—Use a lintel in brick veneer and brick and block types of wall to support the bricks or blocks above the opening. Do not allow the wall case to be used in lieu of a lintel. Flashing—Install flashing (drip rail) as shown to prevent water from dripping inside the wall and down the outside of the building. 2 Support Requirements for the Air Conditioner Mortar between the case and the brick all around the case may be undercut at about 45° for improved caulking. 3 Caulking Top of case Inside Outside Undercut mortar Trim molding (if desired) Plaster line Caulking (above & below the flashing) Flashing (drip rail) 1/4. min. extension inside the wall from the trim molding Room side Brick veneer Lintel angle (if required) Caulking (on all 4 sides on the outside of the case) 22 Notes. 23 Safety Instructions Operating Instructions Care and Cleaning Installation Instructions Troubleshooting Tips Consumer Support Consumer Support Troubleshooting Tips Installation Instructions Care and Cleaning Operating Instructions Safety Instructions Notes. 24 Notes. 25 Safety Instructions Operating Instructions Care and Cleaning Installation Instructions Troubleshooting Tips Consumer Support Before You Call For Service… Consumer Support Troubleshooting Tips Installation Instructions Care and Cleaning Operating Instructions Safety Instructions Troubleshooting Tips Save time and money! Review the chart on this page first and you may not need to call for service. Problem Possible Causes What To Do Air conditioner does not start The air conditioner is unplugged. The fuse is blown/circuit breaker is tripped. Power failure. • Make sure the air conditioner plug is pushed completely into the outlet. • Check the house fuse/circuit breaker box and replace the fuse or reset the breaker. • If power failure occurs, turn the mode control to OFF. When power is restored, wait 3 minutes to restart the air conditioner to prevent tripping of the compressor overload. Air conditioner does not cool as it should Airflow is restricted. The temp control may not be set high or low enough. The air filter is dirty. The room may have been hot or cold. Cold air is escaping. Cooling coils have iced up. • Make sure there are no curtains, blinds or furniture blocking the front of the air conditioner. • Turn the knob to a warmer or cooler setting. The coolest setting provides maximum cooling. The warmest setting provides maximum heating on models with heat. • Clean the filter at least every 30 days. See the Care and cleaning of the air conditioner section. • When the air conditioner is first turned on you need to allow time for the room to cool down or warm up. • Check for open furnace floor registers and cold air returns. • Set the air conditioner’s vent to the closed position. • See “Air conditioner freezing up” below. Air conditioner freezing up Ice blocks the air flow and stops the air conditioner from cooling the room. • Set the mode control at HIGH FAN or HIGH COOL with the temp at a warmer setting. Normal Operating Sounds ¦ You may hear a pinging noise caused by water being picked up and thrown against the condenser on rainy days or when the humidity is high. This design feature helps remove moisture and improve efficiency. ¦ You may hear the thermostat click when the compressor cycles on and off. ¦ Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip from the outdoor side of the unit. ¦ The fan may run even when the compressor is not. 26 Air Conditioner Warranty. All warranty service provided by our Factory Service Centers, or an authorized Customer Care®technician. To schedule service, on-line, 24 hours a day, contact us at or call 800-GE-CARES. Staple your receipt here. Proof of the original purchase date is needed to obtain service under the warranty. For The Period Of: GE Will Replace: One Year From the date of the original purchase Any part of the air conditioner which fails due to a defect in materials or workmanship. During this full one-year warranty, GE will also provi...


Напишите ваш отзыв об устройстве



Текст отзыва
Ваше имя:
Введите две цифры:
capcha





Категории